摘要:In this paper, through the experimental study of two heating seasons, it is found that the heat pump installation position and orientation, circulating pump work/frequency conversion, frosting conditions, etc. have a greater impact on the heat pump unit energy efficiency ratio. According to the actual operation data and theoretical derivation, the analysis shows that the energy efficiency ratio increases by 2.4% when the installation position and orientation increase the air temperature by 1K. The circulating water pump can save 78% of the power consumption in the period by changing the power frequency to frequency conversion. The frosting condition diagram can make a reasonable configuration and operation prediction for the heat pump system.