摘要:In order to make data centers meet the requirements of green data center standards, this paper
starts with air conditioning systems with high energy consumption, and dynamically optimizes airflow
organization. It uses limited space convection heat transfer and air kinematics to dissipate multiple
processes in the data center. The process is solved by MATLAB optimization and reverse demonstration. In
this paper, the influence of cold air flow on cabinet cooling is divided into four key processes: mixing loss
during descent, convective heat transfer in descending process, the convection heat exchange during the
steady flow process, and mixed airflow discharge. By analyzing the temperature change of cold airflow in
each process, and seeking the relationship between velocity v and air resistance F in viscous gas flow, the
temperature-velocity relationship is obtained. Then the relationship between cold loss, PUE value and
indoor height of the data center was analyzed to obtain the ceiling height corresponding to the standard
cabinet height. The best combination is the ceiling height of 3.5m and the cabinet height of 2m and the
corresponding PUE value is about 1.87, which meets the requirements of green data centers and is highly
economical.