首页    期刊浏览 2024年12月02日 星期一
登录注册

文章基本信息

  • 标题:Experimental study on fire-extinguishing efficiency of protein foam in diesel pool fire
  • 本地全文:下载
  • 作者:Wendong Kang ; Long Yan ; Faxing Ding
  • 期刊名称:Case Studies in Thermal Engineering
  • 印刷版ISSN:2214-157X
  • 电子版ISSN:2214-157X
  • 出版年度:2019
  • 卷号:16
  • 页码:1-10
  • DOI:10.1016/j.csite.2019.100557
  • 出版社:Elsevier B.V.
  • 摘要:In order to improve the fire-extinguishing performance of protein foam (PF) in diesel pool fire, a self-built foam extinguishing device was used to explore the influence of gas-liquid ratio, injection angle, driving pressure and liquid flow rate on the fire-extinguishing efficiency of PF. When the gas-liquid ratio is 20, the foam possesses the shortest extinguishing time of 200s and lowest extinguishing agent dosage of 260 g among the samples. Besides, the fire-extinguishing efficiency of PF varies with the change of injection angle and the order is 90° (vertical injection) > 45° (overlooking injection)> −45° (upward injection)> 0° (horizontal injection). In addition, as the increase of liquid flow rate and driving pressure, the fire-extinguishing efficiency of PF increases. In particular, the extinguishing time and the extinguishing dosage agent are reduced by 35.0% and 11.5%, respectively, with the PF flow rate of 50 L/h compared to the case of 20 L/h, which are reduced by 25.0% and 24.6%, respectively, with the driving pressure of 0.5 MPa compared to the case of 0.3 MPa. The factor of fire-extinguishing efficiency of PF was investigated from the experimental aspects, which provided a basis for the application of PF in firefighting..
  • 关键词:Protein foam ; Fire;extinguishing efficiency ; Gas;liquid ratio ; Injection angle ; Liquid flow rate ; Driving pressure
国家哲学社会科学文献中心版权所有