摘要:The problem of vibration and noise of urban indoor substations has becoming more and more socially concerned.The urban indoor substation of 110kV and its conjoined buildings were taken as the research object and the vibration tests of the transformer and each floor slab were respectively carried out.The sound vibration characteristics and sound transmission rules of the urban indoor substation were obtained through the time-frequency analysis and coherence analysis of the test data. The vibration spectrum of transformer body was mainly 100Hz together with its multiplying factors and the vibration characteristics of the floor slab were basically the same as those of the transformer body. it is crucial to control the vibration and noise transmission in the equipment floor of the urban indoor substation.