Distinction between transient and permanent faults using wavelet transform.
Sushama, M. ; Das, G. Tulasi Ram ; Laxmi, A. Jaya 等
Introduction
Auto re-closure schemes as applied to EHV systems have, by offering
benefits such as maintaining system stability and synchronism, been a
major cause of a substantial improvement in the continuity of supply. It
is, however, well known that the present auto re-closure practice
employing a fixed prescribed dead time can pose problems. In the case of
transient faults, for example, a re-strike of a fault due to
insufficient time for the fault path to de-ionise fully can threaten
system stability and reliability and, in case of a permanent fault, a
second shock to the system can cause irreparable damage to expensive
equipment. By W J Laycock C Eng, MIEE, Member IEEE "Adaptive
Re-closure of HV Overhead Lines" IEEE transactions 1996 Rolls-Royce
Industrial Power Group, Reyrolle Protection, Hebburn Tyne and Wear, NE31
1TZ, United Kingdom. Ideally the reclosing is only activated when the
transient fault occurs and the dead time of auto re-closure should be
set in such a way that a re-strike of a fault due to the incompletion of
deionization can be avoided. To do so, distinguishing between transient
and permanent becomes vital important. For this a specifically designed
transient and permanent fault identification unit is used to capture
high frequency current noise generated by the fault arc. Then wavelet
transform is used to distinguish between the transient and permanent
fault by ensuring the presence of secondary arc and the fault sustain
time for a transient fault can be determined.
Wavelet Transform
The wavelet transform is a mathematical tool, much like a Fourier
transform in analyzing time localized stationary signal, which
decomposes a signal into different scales with different levels of
resolution by expanding a single prototype function. Wavelet transform
provides a local representation (i.e. both time and frequency) of a
given signal. Hence it is suitable for analyzing a signal where time-
frequency resolution is needed such as power quality disturbances, where
the characterizing each type of disturbances is different. More
importantly, WT possesses variable windows so that the higher frequency
components can be analyzed employing finer windows to attain more
detailed information and the lower ones are analyzed using wider windows
to get a comparable approximation by Charles K. Chui, " Wavelets: A
Mathematical Tool for Signal Analysis", SIAM, Philadelphia, 1997.
Hence Wavelet has advantages over traditional Fourier Transfor in
analyzing accurately the power system transient phenomena where signals
contain low power frequency and transient such as discontinuities, sags
and sharp spikes.
Circuit Description
Two 735 kV parallel lines, 200 km long, transmit 3000 MW of power
from a generation station (12 generators of 350 MVA) to an equivalent
network having a short circuit level of 20 GVA. The generation plant is
simulated with a simplified synchronous machine. The machine is
connected to the transmission network through a 13.8 kV/ 735 kV
Delta-Wye step-up transformer. The transmission line is double circuit
line feeding 500MW loads. Four circuit breakers are placed in the double
circuit line two at each end of the transmission lines. As long
transmission line has considered, the line models are distributed
parameter lines. The lines are assumed to be transposed and their
parameters R, L, C /km are specified in positive- and zero-sequence
components.
Study of System Faults
The great majority of faults on overhead transmission lines are
transitory in nature. They disappear if the line is de-energized for a
short duration in order to permit the arc to be extinguished. After the
arc has become sufficiently deionise, the line may be reenergized and
put back into use. Lightning is the commonest cause of faults on
overhead lines and most faults caused by lightning are transitory. In
addition some faults due to other causes, such as swinging wires and
temporary contacts with foreign objects are transitory.
A small percentage of the faults on overhead transmission lines are
permanent for example those due to breakage of conductors or poles by
aircrafts, floods, earthquakes or bombs. Rapid reclosure on a permanent
fault is more determined to stability than no reclosure or long delayed
reclosure.
[FIGURE 1 OMITTED]
[FIGURE 2 OMITTED]
The figure 1 and 2 shows the simulated voltage waveforms for a
single phase-to-ground fault with single pole tripping for a transient
fault involving secondary arcing and a permanent fault (with high
impedance)respectively. The former phenomenon arises due to coupling
with healthy phases even after the primary arc has ceased and has a
characteristic waveform presents the typical secondary.
[FIGURE 3 OMITTED]
[FIGURE 4 OMITTED]
Currents of CT's resulting from transient and permanent faults
at the mid-point of transmission line. As indicated in figure 3, when
the fault occurs at time '[t.sub.1]', the great increase of
fault current at the faulty phase 'a' is observed for both
transient and permanent faults. After the relaying time and the breaking
time of CB, the fault is isolated and the faulted current at phase
'a' drops to zero as stated by Z.Q.Bo, R. K. Aggarwal, A. T.
Johns, "A Novel Technique to Distinguish Between Transient and
Permanent Faults Based on the Detection of Current Transients"
APSCOM'95 proceedings of the international conference on advance in
power system control, operation & management, 9-11 November, 1995,
Hong Kong. The analysis shows that only a transient fault generates the
secondary arc which contributes to the broadband high frequency noise on
the transmission line. In contrast no such noise persists in a permanent
fault because of the absence of the arcing phenomenon. This implies that
the detection of the secondary arc can be utilized to ascertain the
instance of the secondary arc extinction time and make the decision for
the re-closure
Simulation Studies
Transient fault is simulated using arc model. The arc model
produces the primary arc and secondary arc. The model is built in MATLAB
using SIMULINK. From a modeling point of view, the fault arc can be
classified into the primary arc during fault duration(before breaker
opens) and the secondary arc which occurs after the breaker trip and
which is maintained by the mutual coupling between the faulted phase and
the sound phases. It has been a long tradition that the primary arc can
be simply represented by an ideal short circuit or by a low value linear
resistance. But the secondary arc is modeled by a nonlinear resistance.
The mean arc resistance is programmed as an exponential function of the
rms current i.e.
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (1)
Mean arc resistance increases when the rms arc current decreases so
that for arc current to decay below the threshold value is shortened.
The arc extinguishes when its rms current falls below a certain
threshold value defined in the arc model block (Fig. 5). The main
factors influencing the secondary arc are wind velocity magnitude and
duration of the preceding primary fault arc current. The secondary arc
is highly complex phenomenon and is influenced by number of factors.
[FIGURE 5 OMITTED]
The Figure 6 shows the simulation model of a transient fault by
considering single phase to ground fault.
[FIGURE 6 OMITTED]
The Figure 7 shows the Simulink model of a permanent model. This
model is simulated by a linear resistor connected to the phase which is
to be faulty. The model is available in simulink/simpower system as
three phase fault.
[FIGURE 7 OMITTED]
Operation of The Transient and Permanent Fault Identification Unit
(TPIU)
To identify the different type of faults, the Daubechies wavelet
transform is utilized to attain the details of high frequency noise
ignitioned by fault arc. The results from Fig. (8) to (11) indicate the
approximation and details of transient fault, while those from figure 12
to 15 represent the approximation and details of transient fault by
F.Jiang, Z.Q. Bo, Q.X. Yang "The wavelet transform applied to
distinguish between transient and permanent faults" IEEE
transactions, 1998. By examining the figures, it turns out that the
fault inception, the Circuit Breaker (CB) opening time and arcing
extinction are well localized at 't1', 't2' and
't3' as shown in figures 8 and 11. It is also noticeable in
transient fault that after single pole CB is opened, the high frequency
noise due to the reignition of fault arcing occurs at approximately
every half cycle. In contrast, no such noise appears in the permanent
fault.
[FIGURE 8 OMITTED]
[FIGURE 9 OMITTED]
[FIGURE 10 OMITTED]
[FIGURE 11 OMITTED]
[FIGURE 12 OMITTED]
[FIGURE 13 OMITTED]
[FIGURE 14 OMITTED]
[FIGURE 15 OMITTED]
Furthermore it is apparent that there is no significant difference
between the transient and permanent fault currents at the healthy phases
'b' and 'c'. However investigation reveals that
after completion of CB opening, the transient due to nonlinear arc of
transient fault still couples to the sounded phases 'b' and
'c' and consequently distort the associated current waveform.
[FIGURE 16 OMITTED]
[FIGURE 17 OMITTED]
[FIGURE 18 OMITTED]
[FIGURE 19 OMITTED]
In contrast, the permanent fault doesn't have such distortion
in the unfaulted phase currents.
[FIGURE 20 OMITTED]
[FIGURE 21 OMITTED]
[FIGURE 22 OMITTED]
[FIGURE 23 OMITTED]
Conclusions
This paper presents a new technique for transient and permanent
fault identification. In contrast to the conventional approach in which
the fault generated high frequency spurious noise is removed by
extensive filtering process. The disadvantages of conventional scheme
are (1). The dead time may be unnecessary long and (2). CB at the
faulted phase may be reclosed under the permanent fault. The former
probably causes instability of interconnected system, while the latter
may damage the CB because of excessive high making current. The present
technique utilizes the noise, to effectively distinguish transient from
permanent fault and to detect the extinguish time of the secondary fault
arc, thereby, significantly enhancing the accomplishment of a successful
re-closure operation.
Annexure
Transient LLG fault
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
Permanent LLG Fault:
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
[ILLUSTRATION OMITTED]
Reference
[1] Z.Q. Bo, RK Aggarwal, A.T. Johns, "A Novel Technique to
Distinguish Between Transient and Permanent Faults Based on the
Detection of Current Transients" APSCOM'95 proceedings of the
international conference on advance in power system control, operation
& management, 9-11 November, 1995, Hong Kong.
[2] F. Jiang, Z.Q. Bo, Q.X. Yang "The wavelet transform
applied to distinguish between transient and permanent faults" IEEE
transactions, 1998.
[3] W J Laycock C Eng, MIEE, Member IEEE "Adaptive Reclosure
of HV Overhead Lines" IEEE transactions 1996 Rolls-Royce Industrial
Power Group, Reyrolle Protection, Hebburn Tyne and Wear, NE31 1TZ,
United Kingdom.
[4] Z. Q. Bo, R.K. Aggarwal, A.T.Johns, B.H.Zhang, Y.Z.Ge, "A
New Concept In Transmission Line Reclosure Using High Frequency Fault
Transients", IEEE Proc-Gener. Transm. Distrib., Part C, Vol. 144,
Sept., 1997.
[5] C.H.Kim, S.P. Ahn, R.K. Aggarwal, A.T. Johns "A novel
concept in adaptive single pole auto-reclosure as applied to high
voltage transmission systems." APSCOM'2000 Proceedings of the
5th International Conference on Advances in Power System Control,
Operation and Management, APSCOM 2000, Hong Kong, October 2000.
[6] Charles K. Chui, " Wavelets: A Mathematical Tool For
Signal Analysis", SIAM, Philadelphia, 1997.
[7] Z Q Bo, A T Johns, "Transient Based Protection--A New
Concept in Power System Protection", IPST'97, International
Conference on Power System Transients, University of Washington,
Seattle, Washington, USA, June 22-26, 1997
M. Sushama (1), G. Tulasi Ram Das (2) and A. Jaya Laxmi
(1) Associate professor, Department of Electrical and Electronics
Engg., JNTU College of Engineering, Hyderabad, Andhra Pradesh, India.
E-mail:
[email protected],
[email protected]
(2) Professor, Department of EEE, JNTU College of Engineering,
Hyderabad, Andhra Pradesh, India