Partial discharge analysis in high voltage rotating machines using BPN algorithm.
Sathiyasekar, K. ; Thyagarajah, K. ; Krishnan, A. 等
Introduction
The life of an electrical machine is mainly dependant on the life
of its insulation. Therefore the aging process of the machine has to be
very closely monitored. Just like the pulse rate, the blood pressure,
sugar level etc, of a human are indicative of his health condition, the
capacitance, leakage current, dissipation factor, polarization index,
surge voltage with standing strength and partial discharge factors are
indicative of the insulation condition of an electric rotating machine.
The insulation is getting weakened by frequent over load conditions for
long periods. This happens due to over load current because of over
load, low voltage, single phasing etc., against which the winding can be
protected by embedding thermal sensors in the winding incorporating over
current sensors and single phasing preventer.
Typically a new machine of 11 kV, 3.75 MW capacity costs about Rs
35, 00,000 /-. By strict periodic preventive maintenance its minimum
life expectancy is not less than 10 years. The annual maintenance cost
is about Rs 60,000.
Including the cost of periodic monitoring of the condition of the
insulation. The installation of the thermal sensors and single phasing
preventer costs about Rs 30,000. Thus spending about Rs 60,000 to 70,000
on annual preventive maintenance saves us from a heavy expenditure of
about Rs 14,00,000 towards the cost of rewinding, if the winding in
burnt out, apart from the loss of production during the lay off period
of rewinding the machine.
Stator winding insulation of generators is prone to partial
discharge (PD) activity as a result of voids within insulation and air
gaps adjacent to insulation under high voltage stress. Partial
discharges are "sparks" involving the flow of electrons and
ions when a small volume of gas breaks down. The term partial is used
since there is a solid insulation, such as epoxy-mica, in series with
the void, which prevent a complete breakdown. Depending on the size of
the void, the dielectric constant, and the temperature, the stress on
the gas within the void may become high enough for breakdown to occur.
In most cases, the electric filed will not be uniform and this will tend
to lower the breakdown voltage.
Partial discharges are often the result of damages caused by other
thermal, mechanical, electromagnetic and chemical stresses acting on the
stator winding. These discharges also contribute to the ageing of the
machine's dielectric system by eroding away or deteriorating the
insulation system. Therefore, partial discharge activity is good
indication of insulation deterioration. Partial discharge testing can
assess the condition of stator winding insulation and thereafter help to
establish a condition based maintenance program. Condition monitoring
and predictive maintenance of stator insulation brings users benefits of
reliable operation, optimal number of maintenance outages and maximal
lifetime of their generators [1].
Electrical Tests on Generator Stator
Carrying out certain nondestructive tests could assess the
progressive deterioration of the insulation of the stator. The test
parameters selected will give useful information regarding the state and
quality of insulation. By monitoring these parameters periodically,
trend in the ageing of the insulation could be assessed.
Insulation Resistance (IR) and Polarization Index (PI) Test
The test reflects the surface conditions of the insulation. In HV
machines, end windings are likely to be affected by moisture and
contamination.
PI is used as an index of dryness and represents cleanliness of the
winding. The test parameters identified are IR after one minute voltage
application and IR after 10 minutes voltage application at 5000 Volts
DC. PI is the ratio of 10 minutes to the one minute value.
Dissipation Factor
The tan [delta] is a valuable quantity that gives integral
information about the condition of the insulation. The tan [delta] is
considered proportional to the total volume of discharging voids, which
increases with the degree of aging. In electrical machines, as in other
electrical equipment, the tan [delta] measurement is used as a
traditional diagnostic method. The dielectric losses in insulation can
be divided into three components, whose sum results in the tan [delta]
of the insulation:
Tan [delta] = tan [[delta].sub.c] + tan [[delta].sub.p] + tan
[[delta].sub.PD] (1)
Where
tan [[delta].sub.c] = the conducting loss factor caused by
free-charge carries, the ions and electrons (conducting losses);
tan [[delta].sub.p] = the polarization loss factor caused by the
polarization processes (polarization losses); and
tan [[delta].sub.PD] = the partial discharge loss caused by PD in
the insulation (ionization losses).
In practice, in high voltage rotating machines, it is very
significant that, in addition to the absolute value of tan [delta] at a
certain test voltage, the tan [delta] as a function of the applied test
voltage, e.g. from 0.2 to 1.2[U.sub.N], is measured at two designated
voltages is named del tan delta ([DELTA]tan [delta]) or tip-up.
In good insulating systems of high voltage rotating machines, the
change in tan [delta] is very small with increasing applied test
voltage. But, an increase in the number and size of the voids or the
information of delimitations in the insulating system during its service
life caused by different stresses can lead to a large increase in the
value of tan a with applied voltage [6].
Capacitance
In absence of cavities or voids within a solid insulation the
change of the capacitance with test voltage is inconsiderable. In
presence of voids within the insulation the occurrence of a partial
discharge within these voids can ionize the gas for several
milliseconds. The ionized gas has sufficiently high conductivity that
the void is shorted out. This means that the effective thickness of
insulation is reduced which leads to an increase of the capacitance.
However, one void shorted out by PD will have no measurable effect
on the capacitance of the test object, but if there are many voids, all
undergoing PD, then there will be a noticeable increase in the
capacitance.
In this case, as long as an increasing number of voids begin to
undergo to discharge with rising voltage the value of capacitance will
increase continuously. The initial value of capacitance ([C.sub.0]),
which is measured at low voltage, is the capacitance at high voltage is
the capacitance of the solid insulation alone, because the voids have
been shorted out by the PD. By taking the different the capacitance of
the voids can be estimated. Therefore, it should be possible to estimate
the void content within insulation by the capacitance tip-up
measurement.
The electrical stress control coating can also have an influence on
the capacitance measuring results of complete machines. The moisture
content and winding contamination can also increase the initial value of
capacitance ([C.sub.0]). If the end-winding of a stator is polluted with
a partly conductive contamination, then the ground potential of the
stator core partly extents over the end-winding and this increases the
surface area of the capacitor plate [7].
Partial Discharge Measurements
Partial discharges (ionization processes) occur in micro voids and
other inhomogeneties present in the body of the insulation. Partial
Discharges also occur in gas gaps between stator bar surface and core
and in the end winding area. The occurrence of insulation deterioration
mechanisms can be determined by measuring partial discharge activity in
the winding.
These discharges cause thermal ageing, mechanical erosion and
chemical deterioration at localized defect sites leading to failure. In
this test, partial discharge magnitudes of the highest partial discharge
pulses at various voltages are measured.
Leakage Current Test
The test voltage is applied in steps and the leakage current is
measured after maintaining the voltage for 1 minute duration in order to
separate the conduction current and the dielectric absorption current.
It is generally believed that imminent failure can be predicted from
marked rise in the conduction current as the test voltage is raised.
Surge Comparison Test
The Capacitance, Tan delta and Partial Discharge measurements are
adequate for testing winding insulation to ground but not the insulation
between turns. Surge testing is an accurate method of identifying inters
turn faults.
Surge voltage is applied on a winding consisting of a number of
coils which in turn consist of many turns. A ringing pattern is seen on
the CRT. The fast raising pulse spreads along the coil and creates a
voltage gradient along the turns. Since the three phases are wound
identically comparing all the phases will show the same single pattern
Fig (1). In case of faults in any one of the phases, the wave pattern
gets separated indicating a fault.
Experiment on Stator Coils
The measurement of dissipation factor and capacitance tip-up was
done by using Schering Bridge at different test voltage at a frequency
of 50Hz. The stator coils used for this investigation being to an
insulating system with a rated voltage of 11kV.
The insulation is based on the resin rich technology. The coils are
finished with semi-conducting anti corona varnish and stress grading
tape to prevent partial discharges Fig (2). In practice the electrical
stress plays the main role in the development of insulation
deterioration and the final breakdown, while other stresses such as
thermal, mechanical, thermo-mechanical and environmental stresses are
mostly the inception factor for creation of defects in insulating
systems.
The electrical stress can cause partial discharges in voids and
cavities, which erode insulating materials and may lead to electrical
treeing, which is often referred to as the most important degradation
mechanism in solid insulation. Therefore, the ability of detection of
such deterioration processes is very important and it is necessary to
investigate the characteristic parameters, which are able to describe
the condition of the insulation [2].
[FIGURE 1 OMITTED]
[FIGURE 2 OMITTED]
The experimental results on the simple epoxy resin specimens
confirm that the relative volume of the air-filled voids within
insulation can be estimated from the changes of capacitance as a
function of the applied voltage [3].
Back Propagation Network
[FIGURE 3 OMITTED]
Architecture
Fig 3 shows a three layer neural network suitable for training with
BPN algorithm. The input (first) layer serves only as distribution
points; they perform no input summation.
The input signal is simply passed to the weights on their outputs.
Each neuron in the subsequent layers produces output signals according
to the activation function used. A neuron is associated with the set of
weights that connects to its input. This network is considered to
consist of three layers. The input or distribution layer is designated
as layer 0, the second layer called hidden layer is denoted as layer 1
and the output layer as layer 2.
The activation function used in the BPN is the sigmoidal function.
Training is generally commenced with randomly chosen weight values.
Typically, the weights chosen are small (between -1 and +1 or -0.5
and +0.5), since larger weight magnitudes may drive the output of layer
1 neurons to saturation, requiring large amounts of training time to
emerge from the saturated state. The learning begins with the feed
forward recall phase. After a single pattern vector x is submitted at
the input, the layers responses z and y are computed in this phase.
Then, the error signal computation phase follows. The error signal
vector must be determined in the output layer first, and then it is
propagated toward the network input nodes. Negative gradient descent
technique is used for calculation of the error factor and for the
calculation of the weight matrix adjustment. First, the weight matrix
connects the hidden layer and the output layer is adjusted and then the
weight matrix connects the input layer and the hidden layer is adjusted.
The training is stopped if the cumulative error is within the limit
or the number of training epoch reaches a maximum set value. The raining
algorithm for the BPN network is given later in this chapter [4].
Sigmoidal Activation Function
The sigmoidal function relates the output of a neuron to the
weighted input or net input (y) as follows;
f(y) = 1/1 + [e.sup.(-y)] (2)
for binary sigmoidal function.
f(y) = 2/1 + [e.sup.(-y)] - 1 (3)
for bipolar sigmoidal function[5].
An Overview of Training
The objective of training the network is to adjust the weights so
that application of a set of inputs produces the desired set of outputs.
For reasons of brevity, these input-output sets can be referred to as
vectors. Training assumes that each input vector is paired with a target
vector representing the desired output; together these are called a
training pair. Usually, a network is trained over a number of training
pairs. The activation function used for the analysis is bipolar
sigmoidal function.
Choice of Learning Rate and Momentum Factor
Weight changes in BPN networks are proportional to the negative
gradient of the error; this guideline determines the relative changes
that must occur in different weights when a training sample (or a set of
samples) is presented, but does not fix the exact magnitudes of the
desired weight changes. The magnitude change depends on the appropriate
choice of the learning rate [eta]. A large value of [eta] will lead to
rapid learning but the weight may then oscillate, while low values imply
slow learning. This is typical of all gradient descent methods. The
right value of [eta] will depend on the applications. Values between
0.001 and 0.9 have been used in many applications [8].
Back propagation leads the weights in a neural network to a local
minimum of the mean squared error. Possibly substantially different from
the global minimum that corresponds to the best choice of weights. This
problem can be particularly bothersome if the "error surface"
is highly uneven or jagged, with a large number of local minima. To
avoid this, Rumelhart, Hinton and Williams suggested that the weight
changes in the ith iteration of the BPN algorithm depend on immediately
preceding weight changes, made in the [(i-1).sup.th] iteration. The
implementation of this method is straight forward, and is accomplished
by adding a momentum term to the weight update rule,
[[DELTA]w.sub.jk] = [alpha][[delta].sub.k] [z.sub.j](s) +
[eta][DELTA][w.sub.jk] (old) (2.3)
Use of momentum term in the weight update equation introduces yet
another parameter [alpha], whose optimal value depends on the
application and is not easy to determine a prior. A well-chosen [alpha]
can significantly reduce the number of epochs for convergence. A value
close to 0 implies that the past history does not have much effect on
the weight change, while a value closer to 1 suggests that the current
error has little effect on the weight change.
Experimental Results And Discussions
This section illustrates the performance of the proposed procedure
for the classification of PD measurements. For all the experiments, with
the chosen learning rate and momentum factor, the bias for both hidden
and output layers are set to 1. The initial weights are randomized
between - 0.5 and + 0.5[9].
PD measurements from seven machines are used for training the
network. Three machines are of 11kV rating and the rest are of 6.6kV
rating. Finally the network is tested with the eighth machine of 11kV
rating (Table 1).This problem is tested with conventional BPN algorithm.
Three trial sets are used. Each trial weight consists of 10 sets of
randomized weight samples. The performance results are shown in Table 2.
Epoch Vs Error characteristics for one set of randomized weight samples
is shown in Fig 4.
Fig 5-Fig 7 shows that target output and actual output comparison
for the test machine of R, Y & B phases respectively.
[FIGURE 4 OMITTED]
[FIGURE 5 OMITTED]
[FIGURE 6 OMITTED]
[FIGURE 7 OMITTED]
Conclusion
The condition of insulation of stator winding of the rotating
machine is determined by the measurement of leakage current,
capacitance, dissipation factor and partial discharge magnitude. We
analyzed the above said parameters for seven machines by neural network
particularly using BPN algorithm to train the network. Now the above
data of the machine under test are fed to the network. From this the
condition of the insulation of the 11 kV machine under test can be
predicted. This network is found to be suitable for predicting the
results close to the actually measured values.
Acknowledgement
We gratefully acknowledge all the testing facilities extended by
M/s. CORAL REWINDING INDIA Pvt. Ltd., Erode for test facilities and
technical discussion and whole hearted thanks to Er. S.Kanmani, Senior
Engineer, Ericssion Ltd., Coimbatore for having given a lot of ideas in
soft computing areas.
References
[1] Draft IEEE Guide to the measurement of Partial Discharges in
Rotating Machinery, IEEE pp 1434, 1998.
[2] Vicki Warren., et. al., (1998) 'Recent Developments in
Diagnostic Testing of Stator Windings', IEEE Electrical Insulation
Magazine, vol. 14, No. 5.
[3] Binder, E., et. al., (August 2000) 'Development and
Verification Tests of Diagnosis Methods from Hydro generators',
CIGRE 38 session, paris, France.
[4] James A. Freeman et. al., (2005) 'Neural Networks
Algorithms, Application and Programming Techniques', 10th Edition.
[5] Lee, Yang S. 40, 'Modified back-probagation algorithm
applied to decision feedback equalization', vision, Image and
signal processing, IEEE proceedings, volume 153, Issue:6 pp 805-809.
[6] K. Sathiyasekar, et. al., (June 2007) 'Novel Partial
Discharge Analysis in the Stator Winding of 60 MW/11KV Alternator Using
Neural Network', Journal of Technical and Vocational Education,
volume 24, No: 1, pp 61-66.
[7] K. Sathiyasekar, et. al., (Sep-2007) 'A Novel Partial
Discharge Analysis in the Stator Winding Using Neural Network',
IEEE-INDICON 2007 & 16th Annual Symposium of IEEE Bangalore Section,
at CPRI, Bangalore, pp 49.
[8] K. Sathiyasekar, et. al., (Jan-2008) 'Non-Destructive
Testing of Motors by Partial Discharge Method', Resource
Utilization and Intelligent Systems--Second International Conference,
held on Kongu Engineering College, Perundurai, Tamilnadu, India, vol-II,
pp 452.
[9] K. Sathiyasekar, et. al., (Aug-2008) 'Application of BPN
algorithm for evaluating insulation behaviour of high voltage rotating
machines', International Conference on Digital Factory-ICDF 2008,
held on Coimbatore Institute of Technology, Coimbatore, Tamilnadu,
India, pp 124.(Won the Best paper award)
[10] K. Sathiyasekar, et. al., (Aug-2008) 'Assessing the
condition of stator winding insulation in high voltage rotating machines
using BPN algorithm', National Seminar on Reliability & Life
Extension Techniques of Electrical Equipments in power system conducted
by NPTI, Ministry of Power, Govt of India, Durgapur, India, pp 103-109
K. Sathiyasekar (1), K. Thyagarajah (2), A. Krishnan (3) and A.
Ebenezer Jeyakumar (4)
(1) Research scholar, Anna University, Zone-6, Salem.
(2) Principal, PSNA College of Engineering and Technology,
Dindigul.
(3) Dean, KSR College of Engineering, Tiruchengode.
(4) Director, Sri Ramakrishna Engineering College, Coimbatore.
(1)
[email protected]
Table 1: PD Measurement of 11 kV machine (Used to test
the trained network)
Classification of PD Measurements BPN
Input neurons: 3 Functional Inputs: 3
Hidden neurons: 3
Output neurons: 1 Bias: 1
Learning Parameters: Learning Rate = 0.1
Momentum Factor = 0.85
Activation Function: Bipolar Sigmoid
Max Failures: 10 Training Tolerance = 0.59
Test Tolerance = 0.04
3 2 1 Trial No.
5 6 3 Failures
24343 16943 25763 Minimum Epoch
30294 30056 29075 Minimum Epoch
26925 24694 27468 Mean Epoch
1957.50 4945.20 1036.90 Standard Deviation
272.01 193.65 296.51 Minimum Time(Sec)
338.51 343.52 334.63 Maximum Time(Sec)
300.86 282.24 316.13 Mean Time(Sec)
0.00 0.00 0.00 % Mean
Misclassifications
Table 2: Classification of PD Measurements using BPN
Applied Leakage
Phase Ground Voltage Current Capacitance
Terminals in (kV) in (mA) in (nF)
R Y and B 4.40 135.7 99.73
6.60 202.9 99.85
8.80 269.5 99.49
11.0 339.5 100.3
Y B and R 4.40 137.8 101.0
6.60 205.8 100.9
8.80 275.5 101.3
11.0 341.1 100.5
B R and Y 4.40 136.1 99.97
6.60 203.6 100.1
8.80 272.1 100.2
11.0 340.7 100.4
PD
Phase Tan Value Magnitude
in (%) (pC)
R 2.458 1500
2.586 2200
2.923 4800
3.315 6000
Y 2.421 1200
2.549 2000
2.856 4700
3.372 6500
B 2.462 1600
2.592 2200
2.898 4800
3.343 6200