Investigation of drying Geldart D and B particles in different fluidization regimes.
Ng, Wai Kiong ; Tan, Reginald B.H.
Drying of nylon (Geldart D) and expanded polystyrene (Geldart B)
particles in fixed and fluidized beds were studied experimentally and
theoretically. Fluidized bed dryers are sometimes operated at velocities
beyond bubbling fluidization to mitigate against de-fluidization of
surface wet particles. It was found that theoretical analysis using
three different drying methods could predict the constant-drying rate at
such velocities and also across the entire fluidization regimes (fixed
bed, bubbling, slugging and turbulent fluidization) as long as the bed
remains completely fluidized. Results also showed that the theoretical
predictions were accurate beyond previously reported velocity limits in
a laboratory scale dryer. During bubbling fluidization, the cross flow
factor method was used effectively to predict the influence of bubble
phase on drying rates. In the falling-rate period, it is demonstrated
that the drying behaviour of nylon at different gas velocities can be
characterised by a single normalized drying curve.
On a etudie de maniere experimentale et theorique le sechage de
particules de nylon (Geldart D) et de polystyrene expanse (Geldart B)
dans des lits fixes et fluidises. Les sechoirs a lits fluidises
fonctionnent parfois a des vitesses qui vont au-dela de la fluidisation
bullante pour attenuer la de-fluidisation des particules mouillees en
surface. On a trouve que l'analyse theorique a l'aide de trois
methodes de sechage differentes pouvait predire le taux de sechage
constant a de telles vitesses et egalement dans tous les regimes de
fluidisation (fluidisation a lit fixe, bullante, pistonnante et
turbulente) tant que le lit demeure entierement fluidise. Les resultats
montrent egalement que les predictions theoriques sont precises au-dela
des limites de vitesse mentionnees precedemment dans un sechoir a
l'echelle de laboratoire. Lors de la fluidisation bullante, on a
utilise avec efficacite la methode du facteur d'ecoulement
transversal afin de predire l'influence de la phase bullante sur
les vitesses de sechage. Dans la periode de vitesse descendante, on
demontre que le comportement de sechage du nylon a differentes vitesses
de gaz peut etre caracterise par une courbe de sechage normalisee
unique.
Keywords: fluidized beds, drying, de-fluidization, cross flow
factor, large particles
INTRODUCTION
Fluidized beds are frequently selected as processing equipment
because of their excellent heat transfer properties and the ease in
controlling transfer of solids into, out of, and within the process
system. In gas-solids fluidization, fluidized beds have been used most
frequently in drying operations than in any other single application
(Geldart, 1986). The first commercial fluidized bed dryer was installed
in USA in 1948 to dry dolomite or blast furnace slag (Zahed et al.,
1995). Since then, hundreds of fluidized bed dryers have operated
worldwide, primarily for granular materials that can be easily
fluidized, such as sand, grains, chemical crystals and fertilizers.
Vanecek et al. (1966) presented an extensive survey of different
materials (granular, in solutions, suspensions and pastes) that are
dried using fluidized beds.
Despite extensive applications, today's process design of
fluidized bed dryers still requires a laboratory bench-scale set-up to
determine fluidization behaviour and batch drying tests to determine
drying kinetics of a particular system before verification is carried
out on a pilot-scale and/or full commercial-scale (Davidson et al.,
1985; Devahastin, 2000; Kunii and Levenspiel, 1991). Bench-scale batch
drying curves are typically obtained for at least one set of operating
conditions and used to extrapolate drying performance for larger-scale
operations and other operating conditions. To describe these batch
drying curves quantitatively, drying models, such as constant-rate
drying model, falling-rate drying model, liquid diffusion model or
receding drying front model, are chosen and parameters are selected to
fit into the model (Chandran et al., 1990; Mourad et al., 1997; Wantano
et al., 1998). Two or more models are usually used to fit one drying
curve, when different drying periods occur within the same curve. An
alternative approach to describe these batch drying curves
quantitatively is to estimate heat and mass transfer coefficients using
transport equations (Ciesielczyk, 1996; Kerkhof, 1994). Recent research
work has been focused on coupling the relevant theoretical drying models
of the material to be dried (Coumans, 2000) with heat and mass transfer
between the two or three phases inside bubbling fluidized beds
(Burgschweiger et al., 1999; Zahed et al., 1995; Chen et al., 2001).
In industrial polymer production, fluidized bed drying is often the
last but vital operation to ensure good product quality. Low moisture
content in the polymer product is a prerequisite for subsequent
extrusion processes. During the drying process, the fluidized bed is
usually operated in the bubbling regime as the gas bubbles help to
promote good solids mixing. This paper, however, aims to predict the
drying rates at velocities beyond the bubbling regime because such
velocities are often used to overcome process upsets in industrial
practice. Modelling work on drying at such velocities has rarely been
reported. For instance, in nylon production, the particles entering the
fluidized bed dryer are wet and sticky as they have been treated under
cooling water during pelletization. These particles often clump together
and de-fluidize the bed. To mitigate against this problem, higher
fluidizing gas velocities are used to breakup these clumps of particles.
In this work, three theoretical methods are used to model drying rates
of two particle types at a laboratory fluidized bed. The accuracy and
the range of validity of the three methods are discussed. The methods
are based on adiabatic heat-mass balance (Kunii and Levenspiel, 1991),
Chilton-Colburn analogy of heat-mass transfer (Sherwood et al., 1975)
and mass transfer coefficient by Gupta and co-workers (Gupta et al.,
1974; Delvosalle and Vanderschuren, 1985). After surface water is
removed, the characteristic drying curve method is used to model the
drying rates during the falling-rate drying period (Keey and Suzuki,
1974).
EXPERIMENTAL
The objective of the experiments was to measure the drying rates of
wetted nylon and expanded polystyrene (EPS) particles in an
air-fluidized bed and to compare them against those predicted using
theoretical models. These drying rates were measured at different
fluidizing velocities from [u.sub.mf] to 5 x [u.sub.mf], [u.sub.mf]
being the incipient fluidizing velocity of the dry particles.
Experimental Apparatus
The experiments were carried out in a batch fluidized bed dryer
(Figure 1), which was a Pyrex cylindrical column with internal diameter
of 0.05 m and height of 0.8 m. The air distributor was a stainless steel perforated plate. The column was topped by a conical freeboard, 0.15 m
high, inclined at 45[degrees]. In all experiments, the column was filled
with particles at a stationary bed height of 0.1 metre, which was
similar to that in industrial dryers. Before entering the bed, the
fluidizing air was measured by a mass flow meter (Brooks 5863i) and
dehumidified by passing through a column containing a drying agent. In
all experiments, the relative humidity of the inlet and outlet air were
measured using two thermohygrometers (Testo T635) installed at the bed
inlet and outlet. From these measurements, the inlet and outlet
humidities were calculated. A material balance, using the measured
humidities and measured airflow rates gave the drying rates. The
moisture content of particles was calculated using the loss of moisture
as measured by the gain in humidity between inlet and outlet air.
[FIGURE 1 OMITTED]
The set-up was designed to operate across the entire fluidization
regimes from [u.sub.mf] to 5 x [u.sub.mf] ranging from fixed bed,
bubbling, slugging, spouting to turbulent fluidization. For nylon
particles, fluidizing velocities ranged from 0.41 m x [s.sup.-1] to 3.74
m x [s.sup.-1] and for EPS particles, they ranged from 0.26 m x s-1 to
0.76 m x [s.sup.-1]. The corresponding regimes at different velocities
are shown in Table 1. The incipient fluidizing velocity of dry particles
was determined from pressure drop measurements across the air
distributor and fluidized bed surface. The pressure drop through the air
distributor as a function of airflow rate was first measured in an empty
column with no solids using a differential pressure transducer (Flotech
Setra C230). Pressure drop across the fluidized bed was then obtained by
subtracting from this pressure drop at each airflow rate from the total
pressure drop with solids in bed. A plot of this relationship gave the
incipient fluidizing velocity of the dry particles. The measured minimum
fluidization velocities of nylon and both types of EPS particles were
0.74 m x [s.sup.-1] and 0.26 m x [s.sup.-1], respectively. For nylon,
the measured value agreed well within 3% deviation from the theoretical
predictions using Wen and Yu's correlation (Wen and Yu, 1966). For
EPS, the measured value was significantly higher than both calculated
values, which could possibly be due to the presence of surface charges.
Materials and Preparation
Nylon and expanded polystyrene (EPS) were selected as test
materials because they belonged to different particle classes and had
different fluidization behaviour when wet. The dry nylon particle was
elliptical with major and minor diameters of 2.5 mm and 2 mm,
respectively, and had a density of 1140 kg x [m.sup.-3]. Two types of
dry spherical EPS particles were used with average diameters of 1.8 mm
and 2.4 mm and they had the same density of 127 kg x [m.sup.-3]. As
nylon particles were large and dense, they fell into Geldart Type D.
Being smaller and less dense, EPS particles lay below Type B near the
bottom of the standard Geldart diagram (Geldart, 1973). When the
particles were wet, nylon was more readily fluidized as compared with
EPS, which tended to clump together and de-fluidized the bed. All
moisture content data were on a bone-dry basis.
Nylon and EPS samples were prepared with the following procedures.
Nylon particles were soaked in water for nine d at room temperature of
around 22[degrees]C before being dripped dry in a sieve. The moisture
content was determined gravimetrically to be about 20 wt.%. EPS
particles were prepared according to manufacturer's instructions by
"expanding" their sizes from 1 mm to 3 mm in boiling water for
5 min. The EPS particles were then dried in an oven at 100[degrees]C
overnight and hand-sieved using mesh sizes ASTM E-11 #14, #10 and #7 to
obtain two average sizes at 1.8 mm (called EPS-1) and 2.4 mm (called
EPS-2). Next, they were soaked in water at room temperature for 24 h
before being dripped dry in a sieve. The moisture content measured by
gravimetry ranged between 30 and 70 wt.% for EPS-1 and between 15 and 35
wt.% for EPS-2. It was difficult to prepare EPS particles with
consistent moisture contents because the particles tended to clump
together when wet and this led to different quantities of water being
trapped inside the inter-particle voids.
THEORETICAL METHODS
To predict the drying rates of wetted nylon and expanded
polystyrene (EPS) particles in an air-fluidized bed, three theoretical
methods from literature were used to model the constantrate drying
period while the falling-rate period was modelled using the
characteristic drying curve method.
In modelling the constant-rate drying period, all three methods are
based on the same concept: drying rate is determined by the maximum
moisture carrying capacity of inlet air under the following assumptions:
a. Drying takes place in a well-insulated environment, i.e. there
is negligible heat transfer between the fluidized bed and surroundings
via the column wall.
b. As the bed temperature falls from room temperature to adiabatic
saturation temperature of inlet air, the heat loss from the particles
has negligible effect on the drying rate.
c. The evaporation of surface moisture is not hampered by internal
resistance, such as capillary action or diffusion.
e. During bubbling fluidization, the presence of bubbles does not
reduce the drying rate.
The first two assumptions are easily justified using standard heat
transfer correlations. The third can also be verified by measuring the
relative humidity outlet air and ensuring that the outlet air is at
adiabatic saturation. However, the last assumption needs to be verified
by calculating a cross-flow factor. During bubbling fluidization, a
fluidized bed is divided into a bubbling phase containing gas bubbles
and a dense phase containing the remaining fluidizing gas and solids.
Bubbles can pose as a gas by-pass through the bed of particles and
reduces the moisture transport between the particles and the fluidizing
gas. The cross-flow factor [X.sub.b] is defined as the number of times a
gas bubble is fl ushed by the fluidizing gas in the dense phase:
[X.sub.b] = K/[u.sub.b]/[H.sub.max] (1)
The mass transfer coefficient between bubbles and the remaining
fluidizing gas K was evaluated according to the following empirical
correlation for large particles by Sit and Grace (1981). The average
bubble velocity [u.sub.b] and bubble diameter [d.sub.b] taken at mid-bed
height were determined from correlations for Geldart Type B and D
particles given in (Geldart, 1986):
[K.sub.c] = [u.sub.mf]/3 + [(4 x [D.sub.a] x [[epsilon].sub.mf] x
[u.sub.b]/[pi] x [d.sub.b]).sup.0.5] (2)
Computed results showed that at velocities that bubbling
fluidization occurred, the cross-flow factor for nylon was 3.2 and that
for EPS-1 and EPS-2 varied between 12.6 and 3.7, respectively. As
previously shown by Davidson et al. (2001), at cross-factor greater than
three, there was good mixing between the bubbles and the remaining
fluidizing gas and therefore, the bubble phase did not affect the drying
rates. It was noted that the validity of this assumption was strongly
dependent on bed diameter. In an industrial-scale fluidized bed, the
bubbles could grow large enough to act as an effective bypass to reduce
the drying rates.
Adiabatic Heat-Mass Balance--Method 1
Method 1 predicts the drying rate on the assumption that both heat
and mass transfer between the fluidizing air and water on particle
surface occurs at thermodynamic equilibrium (Kunii and Levenspiel,
1991). At equilibrium, the outlet air temperature would be same as the
adiabatic saturation temperature of inlet air, which could be taken from
psychometric charts (Keey, 1978). Using the temperature difference
between inlet and outlet air, the heat given up by the inlet air was
used to determine the drying rate in the following equation:
[M.sub.s] x [d.sub.X]/dt = - A x [[rho].sub.a] x u x [c.sub.pa] x
([T.sub.i] - [T.sub.e])/[DELTA][H.sub.vap] (3)
Chilton-Colburn Analogy of Heat and Mass Transfer--Method 2
Both Methods 2 and 3 were used to calculate the moisture content of
the fluidizing air at bed outlet. By integrating the change in moisture
content inside an infinite small volume over the fluidized bed height as
shown in Equation (4), the moisture content was expressed as a function
of bed height (Sherwood et al., 1975)
[p.sub.a] x u x [d.sub.Y] = [h.sub.c] x a/[c.sub.pa] x [Y.sub.e] -
Y(H)] x dH (4)
Based on the Chilton-Colburn analogy between heat and mass
transfer, the mass transfer coefficient of moisture was substituted with
a convective heat transfer term [h.sub.c]/[c.sub.pa] given by following
expressions (Keey, 1978):
[h.sub.c] = [j.sub.H] x [c.sub.pa] x [rho] x u, where (5)
[j.sub.H] = 1.0/[epsilon] x [[Re.sub.p]/(1 - [epsilon])].sup.-0.5].
(6)
By re-arranging Equation (4), the bed height needed to achieve a
given moisture content in the outlet air was expressed in Equation (7):
H = [[rho].sub.a] x [c.sub.pa] x u/[h.sub.c] x a x ln[[Y.sub.e] -
[Y.sub.i]/[Y.sub.e] - Y(H)] (7)
To achieve adiabatic saturation at bed outlet, the bed heights at
different fluidizing velocities were determined theoretically. The
moisture content at adiabatic saturation was a function of the
temperature and moisture content of inlet air and could be taken from
psychometric charts. As long as the bed heights observed during
experiments were higher than the theoretical values, the drying rate
could be calculated using the difference in moisture content between the
inlet air and that at adiabatic saturation.
Mass Transfer Coefficient--Method 3
Method 3 calculates the moisture content of the fluidizing air at
bed outlet using an empirical correlation for the gas-to-particle mass
transfer coefficient, which was verified over a wide range of
experimental data by Gupta, Delvosalle, Vanderschuren and co-workers
(Gupta et al., 1974; Delvosalle and Vanderschuren, 1985). The drying
rate was determined in a similar manner as Method 2, except that the
convective heat transfer term was replaced with the mass transfer
coefficient given by the following correlations:
[k.sub.m] = [j.sub.D] x [Re.sub.p.sup.1.0] x [Sc.sup.-0.667] x
[mu]/[d.sub.p], where (8)
[j.sub.D] = 0.455/[epsilon] x [Re.sub.p.sup.-0.407] (9)
RESULTS AND DISCUSSION
Experimental
Experimental results are illustrated in Figures 2 to 4. The drying
rate of nylon was plotted on the abscissa of the diagrams, and the
fluidizing velocity was the parameter varied.
[FIGURES 2-4 OMITTED]
In drying nylon, Figure 2 illustrated the typical "drying
curve" with an initial constant-rate period followed by a
falling-rate period. Constant-rate drying is usually associated with
removal of free water from particle surface and the falling-rate period
with bound water inside particles. In drying EPS, as the range of
initial moisture content of EPS varied and no constant-rate drying was
observed, the normalized moisture content was chosen as the ordinate to
present a more reflective comparison of drying rates at various
fluidizing velocities.
From Figure 2, it was observed that drying rates of fluidized nylon
particles fall to very low values after a short duration of less than 15
min. To verify that this observation was not due to a lack of
sensitivity in the thermohygrometers in measuring small differences in
relative humidity, drying of single nylon particles was studied using
thermal gravimetric analysis (TGA, Biorad Universal V2.5H). TGA is
highly sensitive to weight loss. Inside the TGA cell, the temperature
was held constant at two different temperatures at 23[degrees]C and
35[degrees]C using purified air as carrier gas at a flow rate of 100 ml
x [min.sup.-1]. The thermo analytical pattern showed an initial steep
fall in drying rate followed by relatively low drying rates. This could
be explained by the evaporation of free water from the particle surface
followed by the slow drying of bound water inside the particles. TGA
results tallied well with those in Figure 2 and verified that the steep
fall in drying rate for nylon particle was not due to a lack of
sensitivity in the thermohygrometers.
Modelling of Experimental Results
Drying of surface water
During the drying of surface water, Methods 1 to 3 were used to
predict the drying rates as a function of the fluidizing velocity and
the results were compared with experimental data as shown in Figures 5
and 6.
[FIGURES 5-6 OMITTED]
Methods 2 and 3 were used to predict the minimum bed heights for
the outlet air to achieve adiabatic saturation at the different
fluidizing velocities. The results of Method 2 showed that the minimum
bed heights range from 0.009 m to 0.410 m for nylon and 0.003 m to 0.052
m for EPS-1 and EPS-2. Method 3 gave values ranging from 0.008 m to
0.151 m for nylon and 0.004 m to 0.032 m for EPS-1 and EPS-2. As all
measured bed heights were higher than these values, the assumption of
adiabatic saturation of the outlet air stream was verified. However, it
should be noted that at very low Reynolds numbers, these kinetic
calculations are prone to over predict drying rates. This well-known
effect of low apparent Sherwood numbers has been resolved by a two-phase
model which incorporated the effect of bypassing and backmixing
(Burgschweiger et al., 1999).
As expected and shown in Figure 5, the drying rates of nylon
particles increased linearly with fluidizing velocity during the
constant-rate period in accordance to Equation (3). All three
theoretical methods were fairly accurate in predicting the drying rates
across the entire fluidization regimes at velocities ranging from
[u.sub.mf] to 5 x [u.sub.mf]. Even though significant changes in
hydrodynamics occurred when the bed changed from fixed bed, bubbling,
slugging, spouting to turbulent fluidization, these changes seemed to
have little effect on accuracy of these three methods. Experimental
results showed that adiabatic saturation was attained at outlet. At
equilibrium conditions, all three methods should lead to identical
results. However, the calculated results for Method 1 were higher by
about 12% as compared to 2.5% deviations from Methods 2 and 3. This was
likely due to inaccuracies arising from reading values off psychometric
charts.
In drying of EPS, the absence of a constant-rate drying period was
likely due to the high sorptivity of porous EPS. The drying rate in the
first period depended not only on the fluidizing conditions but also on
the solid moisture content (Burgschweiger et al., 1999). As a
constant-rate drying period was not observed, the results from Methods 1
to 3 were compared with the initial drying rates measured. As shown in
Figure 6, the experimental results were close to the theoretical values
except at fluidizing velocities of 2.0 x [u.sub.mf] and 2.6 x
[u.sub.mf]. During the first few minutes of the drying process, it was
observed that wet EPS particles clumped together and de-fluidized the
bed. This did not occur for nylon particles. This led to vapour
channelling and spouting, whereby part of the fluidizing air could
bypass the bed. The contact surface area between the fluidizing air and
wet particle surface was therefore lower than that of a well-fluidized
bed. The presence of vapour channelling and lower contact surface area
might have resulted in the lower drying rates measured. Below 2.0 x
[u.sub.mf], it was speculated that the effect of de-fluidization might
not be significant enough to reduce the drying rate as there was more
contact time between fluidizing air and particles. At higher velocity of
2.9 x [u.sub.mf], wet EPS particle clump broke up and the bed entered
the turbulent regime within one to two min. The breaking up of particle
clumps could explain the short dip in drying rates shown in Figures 3
and 4 as the drying process proceeded (normalized moisture content from
1 to 0.7). In the turbulent regime, the drying rate could be predicted
using the three methods.
Experimental results showed that Methods 2 and 3 were accurate
beyond previously reported limits of fluidizing velocities at 1.5 x
[u.sub.mf] and 3 x [u.sub.mf], respectively (Keey, 1978; Gupta et al.,
1974). A good agreement between predicted and measured drying rates can
be seen up to fluidizing velocities of 5.1 x [u.sub.mf] and 2.9 x
[u.sub.mf] for nylon and EPS, respectively.
Falling-rate drying
Beyond the drying of surface water, a characteristic drying curve
method was used to describe the drying rate as a function of moisture
content. The drying rate was normalized with respect to the
constant-rate drying N/[N.sub.c] and was plotted as a function of
normalized moisture content [X.sub.f] given in Equation (10):
[X.sub.f] = X - [X.sub.eq]/[X.sub.cr] - [X.sub.eq] whereby
N/[N.sub.c] = 1 for all [X.sub.f] > 1 (10)
The demarcation point between the constant- and falling-rate period
was used to determine the critical moisture content [X.sub.cr] of nylon
as shown in Geldart (1986). As constant-rate drying was not observed for
EPS, [X.sub.cr] was substituted with the initial moisture content to
calculate the normalized moisture content. The equilibrium moisture
content [X.sub.eq] of nylon was taken as 0.5% according to sorption
isotherm data reported in Kohan (1995). Without known sorption data for
EPS, the equilibrium moisture content was assumed to be zero.
As shown in Figure 7, similar characteristic curves of nylon
particles were obtained across the entire fluidization regimes. Shortly
after reaching the normalized critical moisture content, i.e. [X.sub.f]
between 0.95 and 1, the normalized drying rates fell steeply to very low
values compared to the initial drying rates during the constant-rate
drying period. After the steep fall, these drying rates remained almost
unchanged. The steep fall could be explained by a change in drying
mechanism from evaporation of free surface water to removal of bound
water by diffusion from inside the particles. As nylon has a low water
diffusion coefficient of about [10.sup.-12] to [10.sup.-13] [m.sup.2] x
[s.sup.-1], desorption of bound water was typically governed by Fickian
diffusion (Snaar et al., 1998; Hunt, 1980) and took place very slowly
compared to evaporation of free surface water.
[FIGURE 7 OMITTED]
Unlike nylon particles, the drying behaviour of EPS could not be
predicted accurately with one single characteristic drying curve for all
fluidizing velocities as shown in Figures 3 and 4. This was probably due
to the much lower resistance against the transport of bounded water
inside the EPS to the particle surface. With low internal resistance,
the drying rate depended not only on moisture content but also on the
initial drying rate, the temperature and internal structure of the
material (Keey, 1978). The internal resistance of nylon was so high that
the drying process was largely diffusion-controlled and the rate
depended mainly on the moisture content inside the particles. EPS
particles are porous and have no sharp transition between constant-rate,
capillary- and diffusion-controlled drying periods. In general, it is
difficult to predict the falling-rate period of such porous solids as
considerations have to be given to the internal distribution of moisture
as well as the continual change in temperature of the particles from
wet-bulb temperature to dry-bulb temperature (Keey, 1972). By
normalizing the drying curve of the single particle instead of the
entire bed, Burgschweiger et al. (1999) incorporated the influence of
material hygroscopicity in modelling the first drying period.
CONCLUSION
In the drying of non-porous and large Geldart D nylon particles,
three theoretical methods were used effectively to predict the
constant-rate drying in the complete range of fluidization regimes
(fixed bed, bubbling, slugging and turbulent fluidization) in a
laboratory scale dryer. Results of Methods 2 and 3 were less sensitive
to the accuracy of input parameters as compared with Method 1. In the
drying of porous and sticky Geldart B EPS particles, the theoretical
methods were able to predict the initial drying rates as long as the bed
was completely fluidized. At low fluidizing velocities, the sticky
nature of EPS led to bed de-fluidization, which reduced the drying rate
probably due to vapour channelling and lower contact surface area.
Experimental results showed that both Methods 2 and 3 were able to
predict drying rates up to 5.1 x [u.sub.mf] for nylon and 2.9 x
[u.sub.mf] for EPS, which were higher than previously reported values of
1.5 x [u.sub.mf] for Method 2 and 3 x [u.sub.mf] for Method 3,
respectively. The significance lies in the applicability of these
methods to predict drying rates when fluidizing velocities higher than
those at bubbling fluidization are used to mitigate against
de-fluidization of wet particles.
Using the cross-flow method, it was shown that the bubble phase
would not reduce the drying rate predicted by the three theoretical
methods in a laboratory fluidized bed. Experimental results agreed well
with this prediction.
Using the characteristic drying curve method, a single drying curve
obtained experimentally for nylon particles at one fluidizing gas
velocity was sufficient to predict qualitatively the falling-rate drying
behaviour in different fluidization regimes.
ACKNOWLEDGMENT
The authors are grateful to Seikisui (SEA) Pte Ltd. for providing
the industrial polymer samples.
NOMENCLATURE
a exposed surface of solids per unit volume
[[m.sup.2]/[m.sup.3]]
[c.sub.pa] specific heat capacity of air at constant pressure
[J/(kg x K)]
[d.sub.b] bubble diameter [m]
[d.sub.p] particle volume diameter (diameter of a sphere having
the same volume as the particle) [m]
[h.sub.c] convective heat transfer coefficient between particle
and air stream [J/([m.sup.2] x K x s)]
[j.sub.D] mass transfer j-factor [dimensionless]
[j.sub.H] heat transfer j-factor [dimensionless]
[k.sub.m] true mass transfer coefficient in the dense phase
[kg/([m.sup.2] x s)]
t time taken [s]
u superficial gas velocity (velocity in empty column)
[m/s]
[u.sub.b] bubble velocity [m/s]
[u.sub.mf] minimum fluidization velocity [m/s]
A cross-sectional area of fluidized bed [[m.sub.2]]
[D.sub.a] molecular diffusivity of air [[m.sub.2]/s]
H bed height [m]
[H.sub.max] maximum bed height during fluidization [m]
K overall mass transfer coefficient [1/s]
[K.sub.c] mass transfer coefficient between dense phase
and bubble phase [m/s]
[M.sub.s] dry mass of particles [kg]
N drying rate [kg [H.sub.2]O/(kg solids x s)]
[N.sub.c] drying rate during constant-rate drying period
[kg [H.sub.2]O/(kg solids x s)]
[Re.sub.p] Reynolds number of flow around particle
[dimensionless]
[S.sub.c] Schmidt number [dimensionless]
[T.sub.i] temperature of entering air stream [K]
[T.sub.e] temperature of exit air stream [K]
X moisture content [kg [H.sub.2]O/kg solids]
[X.sub.b] cross flow factor [dimensionless]
[X.sub.cr] critical moisture content [kg [H.sub.2]O/kg solids]
[X.sub.eq] moisture content at equilibrium conditions
[kg [H.sub.2]O/kg solids]
[X.sub.f] normalized moisture content [dimensionless]
Y absolute humidity of air [kg [H.sub.2]O/kg dry air]
[Y.sub.e] absolute humidity of air stream based on adiabatic
saturation of entry air stream [kg [H.sub.2]O/kg dry air]
[Y.sub.i] absolute humidity of entry air stream [kg [H.sub.2]O/kg
dry air]
Y(H) absolute humidity of air stream at height
H [kg [H.sub.2]O/kg solids]
Greek Symbols
[DELTA] [H.sub.vap] heat of vaporization of water [J/kg]
[epsilon] fixed bed porosity [dimensionless]
[[epsilon].sub.mf] bed porosity at minimum fluidization
[dimensionless]
[[rho].sub.a] air density [kg/[m.sup.3]]
[micro] air dynamic viscosity [Pa x s]
REFERENCES
Burgschweiger, J., H. Groenewold, C. Hirschmann and E. Tsotsas,
"From Hygroscopic Single Particle to Batch Fluidized Bed Drying
Kinetics," CJChE 77, 333-341 (1999).
Chandran, A. N., S. S. Rao and Y. B. Varma, "Fluidized Bed
Drying of Solids," AIChE 36 (1), 29-38 (1990).
Chen, Z., P. K. Agarwal and J. B. Agnew, "Steam-Drying of
Coal, Part 2: Modeling the Operation of a Fluidized Bed Drying
Unit," Fuel 80, 209-223 (2001).
Ciesielczyk, W., "Analogy of Heat and Mass Transfer during
Constant Rate Period in Fluidized Bed Drying," Drying Tech. 14 (2),
217-229 (1996).
Coumans, W. J., "Models for Drying Kinetics Based on Drying
Curves of Slabs," Chem. Eng. Proc. 39, 53-68 (2000).
Davidson, J. F., R. Clift and D. Harrison,
"Fluidization," 2nd ed., Academic Press, (1985), pp. 529-561,
695-696.
Davidson, J. F., R. B. Thorpe, O. Al-Mansoori, H. Kwong, M. Peck
and R. Williamson, "Evaporation of Water from Air-Fluidized Porous
Particles," Chem. Eng. Sci. 56, 6089-6097 (2001).
Delvosalle, C. and J. Vanderschuren, "Gas-to-Particle and
Particle-to-Particle Heat Transfer in Fluidized Beds of Large
Particles," Chem. Eng. Sci. 40 (5), 769-779 (1985).
Devahastin, S., "Mujumdar's Practical Guide to Industrial
Drying," Thananuch Business, Thailand (2000), pp 80, 90-91.
Geldart, D., "Types of Gas Fluidization," Powder Tech. 7,
285-292 (1973).
Geldart, D., "Gas Fluidization Technology," John Wiley,
U. K. (1986), pp. 9, 33-54, 17.
Gupta, S. N., R. B. Chaube and S. N. Upadhyay, "Fluid-Particle
Heat Transfer in Fixed and Fluidized Beds," Chem. Eng. Sci. 29,
839-843 (1974).
Hunt, D., "Prediction of Sorption and Diffusion of Water Vapor
by Nylon-6,6," Polymer 21, 495-501 (1980).
Keey, R. B., "Drying Principles and Practice," Pergamon
Press, Oxford (1972)
Keey, R. B., "Introduction to Industrial Drying
Operations," Pergamon Press Oxford (1978), pp. 189-195.
Keey, R. B. and M. Suzuki, "On the Characteristic Drying
Curve," Int. J. Heat Mass Transfer 17, 1455-1464 (1974).
Kerkhof, P. J., "Relations between Local and Effective
Air-Side Mass and Heat Transfer Coefficients in Fluidized Bed
Drying," Drying Tech. 12 (5), 1191-1210 (1994).
Kohan, M. I., "Nylon Plastics Handbook," Hanser/Gardner
Pub., U.S. (1995), pp. 324, 457-459, 511.
Kunii, D. and O. Levenspiel, "Fluidization Engineering,"
2nd ed., Butterworth-Heinemann, Toronto, ON, Canada (1991), pp. 12, 270,
313-336, 415-426, 430-431.
Mourad, M., M. Hemati, D. Steinmetz and C. Laguerie, "How to
Use Fluidization to Obtain Drying Kinetics Coupled with Quality
Evolution," Drying Tech. 15 (9), 2195-2209 (1997).
Sherwood, T. K., R. L. Pigford and C. R. Wike, "Mass
Transfer," McGraw-Hill (1975), pp. 245-247.
Sit, S. P. and J. R. Grace, "Effect of Bubble Interaction on
Interphase Mass Transfer in Gas Fluidized Beds," Chem. Eng. Sci.
36, 327-335 (1981).
Snaar, J. E., P. Robyr and R. Bowtell, "Strong Gradients for
Spatially Resolved Diffusion Measurements," Mag. Res. Imaging, 16
(5-6), 587-591 (1998).
Vanecek, V., M. Markvart and R. Drbohlav, "Fluidized Bed
Drying," Leonard Hill, London, U.K. (1966), pp. 153-165.
Wantano, S., N. Yeh and K. Miyanami, "Drying of Granules in
Agitation Fluidized Bed," J. Chem. Eng. Japan 31 (6), 908-913,
(1998).
Wen, C. Y. and Y. H. Yu, "Mechanics of Fluidization,"
Chem. Eng. Progr. Symp. Ser. 62, 100-111 (1966).
Zahed, A. H., J. X. Zhu and J. R. Grace, "Modelling and
Simulation of Batch and Continuous Fluidized Bed Dryers," Drying
Tech. 13 (1 & 2), 1-28 (1995).
Wai Kiong Ng (1) * and Reginald B. H. Tan (1,2)
* Author to whom correspondence may be addressed. E-mail address:
[email protected]
(1.) Institute of Chemical and Engineering Sciences, 1 Pesek Road,
Jurong Island, Singapore 627833
(2.) Department of Chemical and Biomolecular Engineering, National
University of Singapore, 10 Kent Ridge Crescent, Singapore 119260
Manuscript received January 27, 2006; revised manuscript received
May 31, 2006; accepted for publication August 28, 2006.
Table 1. Fluidization regimes at different velocities
(a) nylon particles
Fluidization velocity Fluidization regime
[m x [s.sup.-1]]
0.41 (0.6 x [u.sub.mf]) Fixed bed
1.70 (2.3 x [u.sub.mf]) Spouting
2.04 (2.8 x [u.sub.mf]) Transition to bubbling
2.55 (3.4 x [u.sub.mf]) Transition from bubbling to turbulent
2.97 (4.0 x [u.sub.mf]) Turbulent
3.40 (4.6 x [u.sub.mf]) Turbulent
3.74 (5.1 x [u.sub.mf]) Turbulent
(b) EPS particles
Fluidization velocity Fluidization regime
[m x [s.sup.-1]]
0.26 ([u.sub.mf]) Fixed bed
0.38 (1.5 x [u.sub.mf]) Bubbling
0.51 (2.0 x [u.sub.mf]) Transition from slugging to turbulent
0.68 (2.6 x [u.sub.mf]) Transition from slugging to turbulent
0.76 (2.9 x [u.sub.mf]) Turbulent