首页    期刊浏览 2024年12月11日 星期三
登录注册

文章基本信息

  • 标题:Using the UPFC and GUPFC Controllers to Maximize Available Transfer Capability (ATC)
  • 本地全文:下载
  • 作者:Rakhmad Syafutra Lubis ; Sasongko Pramono Hadi ; Tumiran
  • 期刊名称:International Journal on Electrical Engineering and Informatics
  • 印刷版ISSN:2085-6830
  • 出版年度:2014
  • 卷号:6
  • 期号:2
  • DOI:10.15676/ijeei.2014.6.2.11
  • 出版社:School of Electrical Engineering and Informatics
  • 摘要:This paper focuses on studying the effect of the unified power flow controller(UPFC) and generalized unified power flow controller (GUPFC) to maximize theAvailable Transfer Capability (ATC). The normalized sensitivity factors technique isused, can be approximately computed, to determine the ATC of a test system,considering a variety of system limits. The basic Voltage Stability Constrain OptimalPower Flow (VSC-OPF) solution that does not consider contingencies is used fordetermining the sensitivity of power flows with respect to the critical loading parameter.Then, based on this solution and assuming a small variation of the loading parameter,compute the power flows again by solving critical power flows function. Then thesensitivity of system loading factor and N-1 contingency criteria technique is used todetermine an optimal location of the UPFC and GUPFC controller. Finally, usingproper models of the UPFC and GUPFC controllers, the effects of this Flexible ACTransmission System (FACTS) controller on the system ATC are studied. The IEEE 57-bus and 118-bus is used as the test system for validity, computing the system ATC for agiven generation and loading pattern. All realistic control limits, as well as voltagedependent loads, are used in the ATC computation, with and without FACTS controller.The GUPFC can so strong influence the system in controlling or enhancement the ATCas good as power flow possible is compared with the UPFC
  • 关键词:UPFC; GUPFC. ATC; loading parameter; VSC-OPF
国家哲学社会科学文献中心版权所有