摘要:A passive residual heat removal heat exchanger (PRHR HX) was used as the research object, and an experimental device with heat conduction oil as the heat source was set up to complete the experimental study of the outside tube saturation boiling. The improved Wilson diagram method was used to calculate the experimental data, and the heat transfer law of the outside tube boiling of smooth tube and finned tube was obtained. Compared with the two types of tubes, the intensification rate of smooth tube was 1.07, and that of finned tube was 2.39, and the finned tube was 2.23 times that of smooth tube. According to the intensification rate, the Nu modification of the heat transfer coefficient of the two tubes was further obtained.