首页    期刊浏览 2024年12月03日 星期二
登录注册

文章基本信息

  • 标题:Experimental Study Performance R-22 AC Split Retrofitted With Propane
  • 本地全文:下载
  • 作者:Imam Ridwan Tanaka ; Berkah Fajar ; Tony Suryo Utomo
  • 期刊名称:MATEC Web of Conferences
  • 电子版ISSN:2261-236X
  • 出版年度:2018
  • 卷号:159
  • DOI:10.1051/matecconf/201815901048
  • 语种:English
  • 出版社:EDP Sciences
  • 摘要:Refrigerant 22 or called R-22 is still the most widely used for air conditioners. However, since it has a relatively high global warming properties, the use of R-22 should be stopped. Refrigerant 290 briefed as R-290 (propane) is the type of refrigerant recommended by many experts for R-22 replacements because the global warming properties of R290 are much lower than R-22. Therefore, in this study the cooling capacity, flow rate mass, power consumed and COP will be evaluated. The air conditioner engine used in this research has 1 PK capacity which is redesigned by adding separator / ducting on various main components of AC. From the result of the study, there are several conclusions revealed: on the same compressor capacity, R-22 cooling capacity is still greater than R290. Meanwhile, the flow rate of R290 is lower than R-22. For power consumption from R-290, it is smaller than R-22. For the value of COP R-290, the value shows greater ie at R-290 on the variation of Incoming Temperature In Evaporator 20°C = 6.23, 23°C = 6.36, 25°C = 6.86, 29°C = 6.20. While at R-22, it shows 20°C = 5.36, 23°C = 6.02, 25°C = 5.76, 29°C = 6.335
国家哲学社会科学文献中心版权所有